Coolant Distribution Unit AL-6
A 4U, 6kW air-to-liquid CDU with redundant variable-speed pumps and PLC-based monitoring.

The AL-6 is a rack-mounted heat-exchange unit for ultra-high-density cold-plate liquid-cooled servers. Its rated cooling capacity is 6kW. Clamp connections simplify installation, while redundant pumps support reliable operation and maintenance. The system manages server cooling and cooling-capacity distribution, with comprehensive real-time parameter monitoring. Redundant RS485 and RJ45 communication interfaces use Modbus RTU and Modbus TCP/IP by default.
Key features
Intelligent flow control
Redundant pump motors use variable-speed control to adjust system flow in response to server load.
System monitoring
PLC control integrates monitoring of temperature, flow, pressure, leakage and liquid level.
Intelligent alarms
A three-level alarm mechanism helps operations staff locate system abnormalities quickly.
Specifications
| Parameter | Value |
|---|---|
| Height | 4U |
| Dimensions | 177 × 481 × 982mm (H × W × D) |
| Rated cooling capacity | 6kW |
| Cooling medium | Primary side: air; Secondary side: specialist coolant |
| Flow | Primary side: 500 m³/h; Secondary side: 0.36 m³/h |
| Maximum rated output differential pressure | Secondary side: ≥1.0bar |
| Rated inlet temperature | Primary side: 25°C; Secondary side: 54.8°C |
| Rated outlet temperature | Primary side: 47°C; Secondary side: 40°C |
| Airflow direction | Front intake, rear exhaust |
| Pump drive configuration | Dual-pump variable-frequency control |
| Maximum power consumption | 300W |
| Power specification | 2 × 1P 220V 50Hz/60Hz |
| External connections | 1″ clamp connections |
| Power connectors | 2 × C14 |
| Communication interfaces | 2 × RS485 & 2 × RJ45 |
| Communication protocols | Modbus RTU & Modbus TCP/IP |
| Refill connection | UQD04 male connection |
| Noise level | 85dB(A) |
Applications
- Liquid-cooled data centres